banner



How To Repair Leaking Sloan Manusl Flushometer

Home / Sloan Majestic Parts Breakdown for Flushometer Repair

Sloan Regal Twoscore Flushometer Parts Breakup and Troubleshooting Guide

Below is the parts breakdown for the Sloan Imperial Flushometer. Scroll downward and click on the function number(s) you need to repair your Royal Flushometer. (Please note: If an particular does non accept a link, nosotros still behave it, simply the detail is not currently on our website. If you wish to order this detail, give usa a phone call.) Scroll by the parts breakdown to see the troubleshooting Q&A, which highlights common problems, and the solutions to fix them. Purple flushometers are one of Sloan's most popular affluent valve systems. Regal units are known for their reliability, seamless design, and high operation.

 Sloan Regal Xl Parts Breakdown PDF

View Consummate Sloan Majestic Flushometer units:
• Sloan 110XL Majestic Closet Flushometer iii.5 GPF
• Sloan 111XL Imperial Closet Flushometer 1.6 GPF
• Sloan 111-1.28XL Imperial Closet Flushometer 1.28 GPF
• Sloan 180XL Majestic Urinal Flushometer 3.0 GPF
• Sloan 186XL Regal Urinal Flushometer 1.5 GPF
• Sloan 180-1XL Regal Urinal Flushometer 1-i/4" Vacuum Breaker i.0 GPF
• Sloan 186-1XL Regal Urinal Flushometer three/4" Vacuum Billow 1.0 GPF
• Sloan 186.05XL Imperial Urinal Flushometer 0.five GPF

  • 1. #08083 - R10 - Chrome Plated Embrace
  • 2. #08050 - A71 - Inside Comprehend
  • iii. #08004 - A19AC - Closet Relief Valve (White)
              #08005 - A19AU - Urinal Relief Valve (Black)
              #08345 - A19ALC - Closet/Urinal Relief Valve (Green)
  • 4. #08003 - A15A - Molded Disc
  • 5. #08002 - A156A - Diaphragm
  • 6. #08006 - A163A - Adaptable Guide (Standard)
              #08252 - A152A - Adjustable Guide (3.5 GPF Closet)
              #08348 - A151A - Adaptable Guide (one.6 GPF Closet)
              #08349 - A155A - Adaptable Guide (1.0 GPF Urinal)
  • vii. #08000 - A38A - 3.v GPF Closet Diaphragm Associates
              #08114 - A41A - i.half-dozen GPF Cupboard Diaphragm Associates
  • eight. #08001 - A37A - one.5 GPF Urinal Diaphragm Assembly
              #08115 - A42A - 1.0 GPF Urinal Diaphragm Assembly
  • 9. #08007 - B50A - Handle Repair Kit (Plastic)
  • x. #08008 - B32A - Chrome Plated Handle Associates
                #08069 - B73A - ADA Handle Assembly
  • eleven. #08054 - A6 - Chrome Plated Handle Nut
  • 12. #08012 - V551A - Vacuum Breaker Repair Kit
  • xiii. #08014 - V500AA - 1-1/ii" ten 9" Chrome Plated Closet Vacuum Breaker
                #08015 - V500AA - one-one/4" x 9" Chrome Plated Urinal Vacuum Breaker
                #08016 - V500AA - 3/four" 10 ix" Chrome Plated Urinal Vacuum Breaker
  • 14. #08020 - 1-1/two" Spud Coupling Gasket Kit for Closet
                #08021 - 1-1/4" Potato Coupling Gasket Kit for Urinal
                #08022 - iii/four" Spud Coupling Gasket Kit for Urinal
  • xv. #08142 - F56A - 1-ane/2" Tater Coupling Assembly
                #08143 - F55A - ane-ane/4" White potato Coupling Assembly
                #08144 - F54A - 3/4" Potato Coupling Associates
  • 16. #08040 - H550 - Tailpiece Coupling Nut
  • 17. #08039 - H551A - Adjustable Tailpiece two-1/16" (Other Lengths Available)
  • 18. #08038 - H552 - Locking Ring
  • nineteen. #08037 - H553 - O-Band
  • 20. #08033 - H543ASD - Control Stop Repair Kit 3/4"
    #08032 - H541ASD - Control Stop Repair Kit for 1" or 3/iv"
  • 21. #08471 - H790A - ane" Screwdriver Stop
                #08469 - H790A - three/4" Screwdriver Cease
  • 22. #80793 - H1012A - Chrome Plated Cover
  • 23. #08023 - 1-one/2" Contumely Spud Assembly
                #08024 - 1-1/iv" Contumely Spud Associates
                #08025 - 3/four" Brass Spud Assembly
  • Complete Units: #08428, #08480, #89791, #08451, #08449, #08453, #08455, #81296

Troubleshooting Q&A

Beneath is a Troubleshooting Q&A Guide for Imperial Flushometers from Sloan. The guide highlights the most commonly occurring problems and how to go about fixing them. As always you can phone call us for aid or if you demand to replace a part and/or unit of measurement.


1

PROBLEM:
Valve closes off immediately

CAUSES:
A) Ruptured or damaged diaphragm.
B) Enlarged by-pass orifice from corrosion or damage.

SOLUTIONS:
A&B) Install new diaphragm or inside parts kit to correct above problems and update flushometer.


2

PROBLEM:
Leaking at Handle Assembly

CAUSES:
A) Handle seal may have deteriorated.
B) Handle gasket has been omitted.
C) Valve is erstwhile mode and handle packing is worn.

SOLUTIONS:
A) Install new seal or handle repair kit. NOTE: The handle seal will easily slide right onto the bushing if information technology is wet.
B) Install A-31 (#08065) handle gasket or handle repair kit B-50-A (#08007).
C) Install handle repair kit B-l-A (#08007).


3

PROBLEM:
Length of Flush too short

CAUSES:
A) Diaphragm assembly and guide associates are non hand tight.
B) Enlarged by-pass orifice from corrosion or impairment.
C) Black urinal relief valve in closet flushometer.
D) Low consumption kit installed in non-depression consumption fixture.
E) Handle assembly is worn.

SOLUTIONS:
A) Screw the 2 assemblies hand tight.
B) Install diaphragm or inside parts kit.
C) Install proper white closet relief valve.
D) Supervene upon with proper inside parts kit.
E) Install handle repair kit B-l-A(#08007).


4

PROBLEM:
Length of Flush too long or fails to close off

CAUSES:
A) Relief valve is not seating properly or by-pass orifice is chock-full considering of foreign textile, or by-laissez passer orifice is closed by an invisible gelatinous film from "overtreated" water.

B) Line pressure level has dropped and is not sufficient to force relief valve to seat.

C) White closet relief valve has been used in a urinal valve.

D) Inside embrace is cracked or damaged.

SOLUTIONS:
A) Detach the working parts and wash thoroughly. Notation: Size of the orifice in the by-pass is of utmost importance in the proper metering of water into the upper chamber of the valve. Do not enlarge or damage this orifice. Replace inside kit if cleansing does not correct trouble.

B) Shut off all control stops until pressure has been restored, then open them once more.

C) Replace with black urinal relief valve.

D) Supervene upon the inside embrace.


5

Problem:
Insufficient volume of h2o to adequately siphon fixture

CAUSES:
A) Command cease not open enough.
B) Urinal valve parts inside a closet valve.
C) Depression consumption valve installed on a non-low consumption valve fixture.
D) Water saver kit installed in old, non-h2o saver bowl.
Eastward) Inadequate book or pressure at supply.

SOLUTIONS:
A) Adjust command stop for desired delivery of h2o.
B) Replace within urinal parts with proper closet valve parts.
C) Replace with proper inside parts kit.
D) Position refill caput on guide so that side i is in up position.
East) If no gauges are available to properly measure supply pressure or volume of water at the valve, so remove the relief valve from the within parts kit, reassemble the valve, and open up the control finish. If the fixture siphons, more h2o book is required. If a 3.5 GPF within parts kit is installed in the valve, then start flip the refill head (nether the diaphragm) to obtain a iv.5 GPF volume. If this volume is however inadequate, remove the flow ring from the guide to obtain a 6.5 GPF volume. If additional flow is withal required, try a low force per unit area guide kit. If fixture does not siphon or if a depression consumption fixture is installed, or if the higher up steps do non evidence satisfactory, steps must exist taken to increase the pressure and/or supply.


6

PROBLEM:
Leaking at top of vacuum billow

Crusade:
A) Rubber vacuum breaker boot or gasket has deteriorated.

SOLUTION:
A) Install new vacuum billow repair kit.


seven

PROBLEM:
Leaking at lesser of vacuum breaker tube or around coupling

CAUSES:
A) Coupling gaskets have deteriorated.
B) Spud washer and/or spud have deteriorated.

SOLUTIONS:
A) Install proper new coupling gasket kit.
B) Install proper new spud washer and/or complete new spud associates.


8

Trouble:
Leaking betwixt valve and command stop

CAUSE:
A) "O" ring and/or locking ring have deteriorated.

SOLUTION:
A) Supercede "O" ring and locking ring simultaneously.


ix

PROBLEM:
Chattering Noise in Flushometer

CAUSES:
A) Diaphragm has been installed upside down.
B) Within cover has get distorted from wear, freezing or abuse.

SOLUTIONS:
A) Replace the segment diaphragm to the proper position equally instructed by markings on the diaphragm.
B) Replace inside cover


Sloan Regal TroubleShooting PDF

View the Sloan Regal XL repair parts or our pick of Sloan affluent valves.

How To Repair Leaking Sloan Manusl Flushometer,

Source: https://sloanrepair.com/pages/sloan-regal-parts-breakdown

Posted by: powelllize1960.blogspot.com

0 Response to "How To Repair Leaking Sloan Manusl Flushometer"

Post a Comment

Iklan Atas Artikel

Iklan Tengah Artikel 1

Iklan Tengah Artikel 2

Iklan Bawah Artikel